The insulation condition of oil-pressboard insulating bushings is commonly evaluated by measuring the dielectric loss factor and capacitance at power frequency. However, systematic investigations into the influence of aging and moisture defects on frequency-domain dielectric spectroscopy (FDS) characteristics are still insufficient. To address this issue, a 10 kV high-voltage FDS measurement system was independently developed. The system has an output voltage range of 0~10 kV and a test frequency band of 1 mHz~10 Hz, with excellent measurement stability and high test accuracy. The standard deviation of dielectric loss of the system is on the order of 10−4 and the relative error is less than 5%. It also features reliable weak current detection capability and thermal stability. Based on this system, the dielectric spectral characteristics of oil-pressboard insulation models with different moisture contents and aging levels were investigated under various temperatures and applied voltages. The results indicate that the dielectric spectrum shifts toward higher frequencies with increasing temperature. Moreover, the low-frequency dielectric loss of degraded insulation increases linearly with the applied voltage, and the rate of increase shows a positive correlation with both moisture content and aging duration. As insulation degradation becomes more severe, the voltage-dependent characteristic frequency moves toward higher frequencies. This frequency refers to the characteristic frequency where the dielectric loss of insulation presents an obvious linear variation with the change of applied voltage. Unaged and dry bushings exhibit only weak voltage dependence at 0.01 Hz, whereas bushings aged for 28 days with a moisture content of 4.121% demonstrate pronounced voltage dependence at 10 Hz. These results provide a valuable technical basis for diagnosing coupled aging and moisture defects in oil-pressboard insulated bushings.
Li et al. (Sun,) studied this question.