March 3, 2026SHILAP Revista de lepidopterología8 citationsOpen Access

Resilience-oriented optimization of hospital microgrids with critical load support using ESS and PV under grid outage conditions

View Full Paper
PNPourya NazartalabHAHosein Alavi-Rad

Key Points

  • Coordinated multi-node battery energy storage placement reduces energy not supplied by 55–63%.
  • Model achieves over 95% supply to life-critical loads, demonstrating effectiveness in grid outages.
  • Mixed-integer linear programming framework optimizes energy storage scheduling across Monte Carlo scenarios.
  • Sensitivity analysis identifies battery capacity, photovoltaic penetration, and outage duration as key resilience factors.

Abstract

Abstract This study develops a resilience-oriented optimization framework for hospital microgrids that integrates photovoltaic (PV) generation, multi-node battery energy storage systems (BESS), and medical load prioritization under grid outage conditions. A mixed-integer linear programming (MILP) model is formulated to jointly optimize ESS scheduling, critical-load support, and renewable utilization across a set of Monte Carlo outage scenarios. The framework introduces a multi-tier hospital load hierarchy (ICU, OR, imaging, pharmacy) based on Value of Lost Load (VOLL), and employs a composite resilience index combining ENS, LOLP, and critical-load survivability. The model is evaluated on modified IEEE 13-, 33-, and 69-bus systems. Results show that coordinated multi-node ESS placement improves resilience significantly, reducing Energy Not Supplied (ENS) by 55–63% compared with baseline configurations, while maintaining ≥ 95% supply to life-critical loads across most stochastic outage realizations. The proposed strategy also ensures stable Resilience Index (RI) values with a variance below 10%, highlighting robustness against PV variability and outage timing uncertainty. Sensitivity analysis demonstrates that ESS capacity, PV penetration, and outage duration are the dominant factors influencing resilience. Overall, the framework provides a practical and quantitatively validated tool for hospital energy planners seeking enhanced survivability and operational security during grid disruptions.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Nazartalab et al. (2026) studied this question.

synapsesocial.com/papers/69a75da2c6e9836116a27d0ahttps://doi.org/10.1038/s41598-026-34992-x
Ask AI
Helpful
Bookmark
Share
View Full Paper

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1A Comprehensive Review on Rectifiers, Linear Regulators, and Switched-Mode Power Processing Techniques for Biomedical Sensors and Implants Utilizing in-Body Energy Harvesting and External Power Delivery2021 · 44 citations
  2. 2Distributed minimum spanning tree approach for critical load restoration using microgrid formation in resilient distribution systems2024 · 19 citations
  3. 3Optimal design of hybrid renewable-energy microgrid system: a techno–economic–environment–social–reliability perspective2024 · 17 citations
  4. 4Energy demand supply of small-scale medical centers in epidemic conditions of Covid-19 with hybrid renewable resources2023 · 8 citations
  5. 5Advances in hospital energy systems: Genetic algorithm optimization of a hybrid solar and hydrogen fuel cell combined heat and power2024 · 30 citations