PulseExploreJournal ClubDebatesTrendingResearchersJournals
Instagram
HomeExploreJournal ClubTrending
Synapse
⌘+K
Synapse
January 22, 2026Energies0 citationsOpen Access

Reinforcement Learning-Based Optimization of Environmental Control Systems in Battery Energy Storage Rooms

View Full Paper
SPSoyeon ParkDKDeun-Chan KimJBJun-Ho Bang

Key Points

  • The aim is to optimize environmental control systems in battery energy storage rooms using reinforcement learning (RL) techniques.
  • Developed an RL-based optimization framework for battery room environmental controls.
  • Implemented and evaluated both value-based (DQN, Double DQN, Dueling DQN) and policy-based (Policy Gradient, PPO, TRPO) RL algorithms.
  • Used one year of real operational and meteorological data sampled at 15-minute intervals for training and evaluation.
  • Assessed performance based on convergence speed, learning stability, and cooling-energy consumption.
  • The DQN algorithm reduced cooling power consumption by 46.5% compared to traditional control systems.
  • Maintained temperature, humidity, and dew-point violations below 1% during the testing period.
  • Policy Gradient showed competitive energy savings but required longer training and had higher reward variance.

Abstract

This study proposes a reinforcement learning (RL)-based optimization framework for the environmental control system of battery rooms in Energy Storage Systems (ESS). Conventional rule-based air-conditioning strategies are unable to adapt to real-time temperature and humidity fluctuations, often leading to excessive energy consumption or insufficient thermal protection. To overcome these limitations, both value-based (DQN, Double DQN, Dueling DQN) and policy-based (Policy Gradient, PPO, TRPO) RL algorithms are implemented and systematically compared. The algorithms are trained and evaluated using one year of real ESS operational data and corresponding meteorological data sampled at 15-min intervals. Performance is assessed in terms of convergence speed, learning stability, and cooling-energy consumption. The experimental results show that the DQN algorithm reduces time-averaged cooling power consumption by 46.5% compared to conventional rule-based control, while maintaining temperature, humidity, and dew-point constraint violation rates below 1% throughout the testing period. Among the policy-based methods, the Policy Gradient algorithm demonstrates competitive energy-saving performance but requires longer training time and exhibits higher reward variance. These findings confirm that RL-based control can effectively adapt to dynamic environmental conditions, thereby improving both energy efficiency and operational safety in ESS battery rooms. The proposed framework offers a practical and scalable solution for intelligent thermal management in ESS facilities.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Park et al. (2026) studied this question.

synapsesocial.com/papers/6971bd90642b1836717e2301https://doi.org/10.3390/en19020516
Ask AI
Helpful
Bookmark
Share
View Full Paper