Synapse
⌘+K
Synapse
PulseExploreClubsResearchersJournals
Instagram
HomeClubsExplore
February 6, 2026Proceedings of the Institution of Mechanical Engineers Part E Journal of Process Mechanical Engineering

Simulation and experimental investigation on performance of heat pump scroll compressor with two-phase vapor injection

View Full Paper
Ask AI
Bookmark
Share

Authors

WWWeitao WangZZZhaorui ZhaoJHJiayi He

Discussion

Loading...

Member takes

Overview

Simulation and experimental investigation reveals vapor injection improves compressor capacity in heat pump systems, suggesting enhanced energy efficiency.

Key Points

  • This research aims to explore how vapor injection techniques affect the performance of scroll compressors in heat pumps, particularly at low temperatures.
  • Developed a thermodynamic model to assess vapor injection effects on compressor performance.
  • Constructed an experimental platform for testing vapor injection scroll compressors.
  • Regulated vapor injection states using electric heaters and studied various refrigerant conditions.
  • Compared simulation results with experimental data to validate findings.
  • During superheated vapor injection, an increase in injection temperature slightly decreased mass flow rates but improved coefficient of performance (COP).
  • During two-phase injection, the mass flow rate increased by 55.87% as injection quality rose from 60% to 90%, with a heating capacity increase of 3.72%.
  • Simulation errors for both vapor injection types remained within 10%.
  • Vapor injection point placement affects performance: near suction increases mass flow and heating capacity, while near discharge reduces COP.

Cite This Study

Wang et al. (2026) studied this question.

synapsesocial.com/papers/698585678f7c464f23008b02https://doi.org/10.1177/09544089251414173
View Full Paper
Ask AI
Bookmark
Share

Also Consider

Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context:

  1. 1Performance comparison of liquid, vapor, and liquid–vapor injection of single-screw compressor for an air-source heat pump2024 · 1 citations
  2. 2Experimental investigation of a two-stage R290 heat pump with economizer and internal heat exchanger: Impact of subcooling and intermediate pressure2026
  3. 3Assessment of key performance indicators for a reciprocating compressor with electronically controlled vapor injection2026 · 1 citations
  4. 4Performance Comparison of High-Temperature Heat Pumps with Different Vapor Refrigerant Injection Techniques2024 · 5 citations
  5. 5Performance investigation of a quasi-saturated compression high-temperature heat pump system with water-injection2026