To address the unobservability of distribution networks caused by insufficient coverage of measurement terminals as well as communication failures and missing data, and to cope with operating-state fluctuations induced by distributed generation integration and external environmental disturbances, this paper proposes an integrated state-estimation and voltage-regulation strategy that combines distribution-network-partitioning-based optimal PMU placement with pseudo-measurement construction using power transfer distribution factors (PTDFs). First, nodal reactive-power sensitivity information is derived from the power-flow Jacobian matrix, and an improved modularity function is employed to obtain the optimal partitioning of the distribution network, based on which PMUs are deployed at partition boundary buses. Second, PTDF-based power pseudo-measurements are constructed for unobservable buses and incorporated into the measurement model via a measurement transformation; a weighted least-squares method is then adopted to achieve system-wide state estimation. Finally, the estimated voltage states are fed into flexible voltage-regulation devices to enable fast and continuous voltage adjustment across buses. Case studies on the IEEE 33-bus system demonstrate that the proposed method effectively improves voltage quality.
Qu et al. (2026) studied this question.