The Earth–Air Heat Exchanger (EAHE), also referred to as an air–soil heat exchanger, represents an effective passive cooling technology that exploits the thermal inertia of the ground. This study presents a combined experimental and analytical investigation of an EAHE system installed at the Faculty of Sciences of Agadir (Morocco). A steady-state analytical model based on convective heat transfer between the airflow within a buried duct and the surrounding soil is developed to describe the axial evolution of air temperature along the exchanger. The model is formulated under a sensible heat transfer framework, where the influence of humidity is accounted for through its effect on the thermophysical properties of moist air, while latent heat transfer and condensation phenomena are neglected. An instrumented experimental setup was implemented to perform continuous measurements of air temperature and relative humidity over a seven-month monitoring period. The experimental results indicate that the outlet air temperature remains stabilized within the range of 23.5–23.8 °C, despite significant variations in ambient temperature (13–38 °C). A parametric analysis is conducted to assess the influence of duct diameter, airflow velocity, and humidity through its effect on moist air properties on the thermal performance of the system. The close agreement between experimental observations and analytical predictions demonstrates the validity and predictive capability of the proposed model. These findings highlight the potential of EAHE systems as an effective passive cooling solution for greenhouse applications in semi-arid climatic conditions.
Yagour et al. (Tue,) studied this question.