May 4, 2026Energies0 citationsOpen Access

A Study on the Thermal Management Performance of Server-Oriented Memory Liquid Cooling Solutions

View Full Paper
YCYanling ChenZTZhongyun TianMKMingzhi Kong

Key Points

  • To evaluate the thermal management performance of different liquid cooling solutions for memory in high-density servers.
  • Three types of liquid cooling solutions were experimentally compared: water-flowing cold plate, clamp-type cold plate, and heat-pipe-based cold plate.
  • Experiments were conducted at coolant inlet temperatures of 37–50 °C with a fixed flow rate of 0.8–1.5 L/min.
  • Measurements included memory, CPU, voltage regulator temperatures, and system pressure drop.
  • Memory temperature increased with coolant inlet temperature for all configurations, ranging from 62.04 to 76.07 °C depending on the solution.
  • Pressure drops varied from 24.19–35.98 kPa across the three cooling solutions.
  • Relative thermal performance among the configurations remained unchanged despite varying temperatures.

Abstract

The rapid increase in memory power density has made memory thermal management a critical challenge in high-density servers, where extremely limited DIMM spacing significantly reduces the effectiveness of air cooling. Compared with CPUs and GPUs, memory-level liquid cooling has received less systematic study, particularly regarding the influence of cold plate structural design on thermal and hydraulic performance under realistic server conditions. In this paper, three engineering-feasible memory liquid cooling solutions (water-flowing cold plate, clamp-type cold plate and heat-pipe-based cold plate) are experimentally compared on a high-density server system. Experiments are conducted at coolant inlet temperatures of 37–50 °C with a fixed flow rate of 0.8–1.5 L/min. Memory, CPU, and voltage regulator temperatures, as well as system pressure drop, are measured. Results show that memory temperature increases with coolant inlet temperature for all configurations, while their relative performance remains unchanged. Memory temperatures range from 62.04 to 71.13 °C, 57.65 to 66.98 °C, and 66.22 to 76.07 °C, with corresponding pressure drops of 24.19–26.69 kPa, 32.73–35.98 kPa, and 27.00–29.96 kPa. These results provide insight into the role of coolant distribution and flow-path topology in memory thermal performance.

Ask AI
Helpful
Bookmark
Share
View Full Paper

Cite This Study

Chen et al. (2026) studied this question.

synapsesocial.com/papers/69f836d93ed186a739980f72https://doi.org/10.3390/en19092150