This paper proposes a continuous inertia estimation framework for transmission-level power systems with high renewable energy penetration, using a battery energy storage system (BESS) as a controllable small-signal power injection source. The proposed framework integrates BESS-based active power injection, a two-stage signal-smoothing scheme, and a rate-of-change-of-frequency (RoCoF)-based estimation mechanism to enable continuous inertia estimation without relying on major disturbance events. With noise-robust processing and moving-window analysis, the framework can reliably track inertia variations under noisy measurement conditions and diverse operating scenarios. The framework is validated on the IEEE 39-bus system under renewable energy source (RES) penetration levels of 0%, 10%, 20%, and 30%. The estimation error remains within ±3.5% across all scenarios, ranging from 1.26% at 0% RES penetration to 3.43% at 30% penetration. In addition, the estimated inertia closely follows the theoretical decrease from 3.20 s to 2.22 s as RES penetration increases. These results demonstrate the accuracy and robustness of the proposed framework for continuous inertia monitoring in low-inertia power systems with high-RES penetration.
Chang et al. (2026) studied this question.