• A valve-side single-phase-to-ground fault of the MMC converter transformer causes fault-induced inrush current. • Fault-induced inrush current causes voltage distortion on LCC inverter ac bus, leading to subsequent commutation failures. • Subsequent commutation failures aggravate the sympathetic inrush current caused by fault-induced inrush current. • Enhanced sympathetic inrush current causes the incorrect blocking of current differential protection. The scheme based on hybrid submodules against valve-side faults is adopted to mitigate fault-induced inrush current.
Building similarity graph...
Analyzing shared references across papers
Loading...
Tao Zheng
North China Electric Power University
Yuting Xue
North China Electric Power University
International Journal of Electrical Power & Energy Systems
North China Electric Power University